RM AirSeT Gas Insulated Switchgear

RM AirSeT Gas Insulated Switchgear

$1.00
跳至产品信息
RM AirSeT Gas Insulated Switchgear

RM AirSeT Gas Insulated Switchgear

$1.00
Insulation and Disconnection
Switching Technology Parallel Vacuum Interruption Technology (SVI) TM or Vacuum Circuit Breaker
Operational Principle 3-station Load Switch
Disconnect the Medium Vacuum Arc Extinguishing Chamber
Insulation Medium Dry Air(1)
Relative Inflation Pressure 20℃, 12kV MPa 0.04
Insulation Level – Withstand Voltage
Rated Voltage Ur kV 12
Rated Frequency fr Hz 50
Rated Power Frequency Withstand Voltage Ud Alternate Phases
&
to Earth
kV 42
Across the Isolating Distance (1min RMS) 48
Rated Lightning Impulse Withstand Voltage Up Alternate Phases
&
to Earth
kV 75
(1.2μs)
Across the Isolating Distance 85
Current
Rated Current—Busbar Ir Meet 1.1 Ir 630A
Short-time Withstand Current Ik kA 20
Duration tk/tke s 4s/3s
Rated Peak Withstand Current Ip kA 50
Protection Degree
External Shell in Accordance with GB/T 4208 Standard Air Box IP67
Cable Room IP4X
Mechanism Room IP4X
Low Voltage Room IP4X
Internal Compliance with GB/T 4208 Standard Compartment IP2X
Mechanical Impact Protection Level
IK Code Meets the GB/T 20138 Rating IK07
Internal Arc Fault Tolerance
Basics Not Classified
A-level A FL Front and Side kA 20
A FLR Front, Side and Back kA 20
Duration s 1s
Recycling Precautions
Non-recyclable Parts: Maximum Ratio of Volume/Weight (Solid Insulation, Spray Materials…) <1%/<5%
Other Materials (Steel, Stainless Steel, Copper, Aluminum, Recyclable Composite Materials…) 100% Recyclable
Specific Processing Procedures for Gas Operation/Recovery No Harmful Gases (air only)
No SF6 Technology Gas Insulated Switchgear: Housing Definition Meets GB/T 3906 Standard Yes – Seal Pressure System GIS
Service Life Year 40(2)
Note:
(1) Pure air from the factory (dried, filtered, pressurized) does not require further air replenishment.
(2) Under normal usage conditions specified in GB/T11022